HomeProductsHYPCS Series Isolated Three-Phase Energy Storage Converter

HYPCS Series Isolated Three-Phase Energy Storage Converter

The HYPCS isolated three-phase energy storage converter provides bidirectional conversion between battery energy storage and AC power systems. Its isolated architecture supports grid-connected and off-grid operation, scheduled charging and discharging, reactive-power support and optional harmonic compensation for industrial microgrids, renewable-energy projects and critical-power applications.

Model Description

  • W/A: Water cooling / Air cooling
  • S: Single-phase / Three-phase
  • T: Delta / Wye connection
  • H: Harmonic compensation / Without harmonic compensation
  • O: Outdoor type / Indoor type
  • Grid voltage level: 6 kV; 10 kV; 35 kV
  • PCS output voltage: 0.4–0.4 kV
  • Rated power range: 50 kW – 500 kW; 2.0 MW – 2 MW
  • C: Isolated type
  • PCS: Power Conversion System

Key Features

  • Advanced energy storage coordination control
  • Fast fault detection technology
  • Complete isolation between grid and load
  • Harmonic compensation and reactive power support
  • High power factor, stable charging/discharging performance
  • Grid-connected/off-grid seamless switching (with optional zero-crossing control)
  • Flexible time-segmented charging/discharging function, configurable to site requirements

Technical Parameters

Parameter Specification
Rated Grid Voltage 400 VAC (340–460 VAC)
Rated Frequency 50/60 Hz
Rated Output Power 50 / 100 / 250 / 500 kW
Max. Output Current 79 / 159 / 397 / 794 A
Overload Capacity 1.1 × rated current (long-term)
Topology Three-level NPC
Max. Output Power 57.6 / 114.1 / 282.9 / 558.4 kW
Max. DC Current 288 / 228 / 566 / 1117 A
DC Voltage Range 200–600 VDC or 500–900 VDC
Power Factor –1 to +1 adjustable
Current Harmonics (THDi) <3% (rated output)
Output Voltage Accuracy 1%
Max. Efficiency 95.5% / 96.4% / 97.2% / 98.5%
DC Ripple Supported
Parallel Operation Supported
Communication Interfaces RS232 / RS485 / Ethernet / GPRS (optional)
Altitude Up to 4000 m (derating required above 4000 m)
Protection Level IP20
Operating Temperature –25°C to +55°C
Cooling Method Intelligent air cooling
Installation Indoor installation
Dimensions (W×D×H mm) 250kW: 1000×2000×800; 500kW: 1400×2000×1000
Note:
  1. Dimensions are for reference only, subject to actual delivered product.
  2. Specifications may be updated; please confirm the latest parameters when ordering.