ENGINEERED SOLUTION
Steel & Metallurgy
Power factor correction, harmonic mitigation and voltage support for electric arc furnaces, rolling mills, cranes and high-load metallurgical production lines.
| Parameter | Specification |
|---|---|
| Rated Voltage | 380 V, three-phase |
| Rated Capacity | 30 / 45 / 60 / 90 kvar (customizable per user requirements) |
| Compensation Mode | Three-phase balanced compensation; Three-phase individual compensation; Three-phase hybrid (balanced + individual) compensation |
| Fixed Compensation | Optional fixed capacitors available on request |
| Control Parameter | Reactive power |
| Dynamic Response Time | Mechanical switch: ≤0.25 s; Integrated electronic switch: ≤20 ms |
| Permissible Voltage Deviation | –15% ~ +10% (steady operation maintained up to 418 V) |
| Protection Functions | Over-voltage, under-voltage, phase loss (using PDC-8000 comprehensive control unit), harmonic overload, unbalanced voltage, and more |
| Automatic Operation | Automatic recovery within 10 s after fault removal or power restoration |