Passive harmonic filters · IEEE 519 / IEC 61000

From system model to a bid-ready filter design.

HY-PQD Studio is an engineering platform for passive harmonic filters and reactive compensation. Model the network, run the harmonic study, size single-tuned, high-pass and C-type branches, verify the limits, and issue the calculation book — in one consistent project.

3Assessment frameworks
6Interface languages
2–50Harmonic orders
10Branches per project
System modeling · English UI
HY-PQD Studio system modeling screen with project data, PCC parameters and live calculation results
One source of truth. PCC and supply data drive the short-circuit, impedance and compensation figures shown on the same screen.
Voltage THD · before → after
2.97% → 1.17%
IEEE 519-2014 limit 5.0% at the PCC
Configured compensation
3,388 kvar
4 branch groups · 3,282.84 kvar at the operating point
Order-by-order result
49 / 49
Individual current and voltage checks passed
Reference project
11 kV
481.6 MVA short-circuit · 25.28 kA
One model, one engine

The single-line diagram is the calculation model.

There is no second spreadsheet to keep in sync. Source impedance, transformer, cable, loads and filter branches are entered once; power flow, harmonic penetration, impedance scans and limit checks all read the same network.

  • ✓System-level inputs. PCC voltage, short-circuit capacity, Isc, X/R or phase angle, supply capacity and target power factor.
  • ✓Live calculation. Short-circuit current, system impedance and required kvar update as the model changes.
  • ✓Traceable results. Every branch current and voltage result can be traced back to the topology that produced it.
Load list with active power, natural and target power factor, compensation, current and status
Platform capabilities

Built for the engineering decisions that decide the scheme.

Six capabilities cover the path from network data to a checked, exportable filter design — without splitting the study across unrelated tools.

01

System-level modelling

Represent the PCC, supply, transformer, cable, load groups and compensation in one network. Enter short-circuit capacity, Isc, impedance angle and target power factor once.

02

Power flow and harmonic simulation

Run power flow, harmonic penetration and impedance scanning from the same model. See branch flows, PCC voltage deviation and the harmonic spectrum before and after filtering.

03

Multi-branch filter design

Configure up to ten filter branches in one project, mixing single-tuned, high-pass and C-type structures. Set series sections, parallel units, star or delta wiring, capacitor voltage rating and tuning margin.

10 branches · 2–50 orders
04

ETAP and CAD exchange

Import and export ETAP topology data, and export the single-line diagram to DXF. The drawing and the calculation model stay on the same data path.

05

Multi-standard assessment

Evaluate IEEE 519-2014 as the primary framework, with IEC 61000-3-6 and IEC 61000-3-12 planning levels for international projects. GB/T 14549 remains available where the local authority requires it.

06

Calculation book and six languages

Generate a Word proposal and an Excel calculation book with parameters, branch design, simulation results, limit checks and conclusions. The interface is available in English, Chinese, Japanese, French, Russian and Spanish.

Workflow

Five steps from network data to a signed calculation book.

The sequence is deliberately short. Each step consumes the output of the previous one, so the final report cannot drift away from the model that produced it.

STEP 01

Model the supply and the PCC

Enter voltage level, short-circuit capacity, Isc, supply capacity, transformer location and target power factor. The platform returns system impedance, compensation capacity and expected THDu immediately.

STEP 02

Build the topology and the load list

Place the PCC, transformer, cable, load groups and filter branches on the single-line diagram. Each load carries active power, natural power factor, target power factor, compensation and current.

STEP 03

Design the filter branches

Choose single-tuned, high-pass or C-type branches; set tuning order, series sections, parallel units, wiring and capacitor voltage rating. The platform calculates capacitance, reactance, fundamental output and branch loading.

Filter design results table with tuned order, filter type, branch capacity and rated current
STEP 04

Verify the result, order by order

Run the harmonic simulation and check current distortion, voltage distortion and every harmonic order against the selected limits. Impedance scans expose resonance points before they become a site problem.

Order-by-order harmonic assessment table with current, voltage and pass results
STEP 05

Issue the calculation book

Export the Word proposal, Excel calculation workbook, CSV summary and DXF drawing. The package carries the same project data, branch design and compliance conclusion.

Product walkthrough

Eight screens. One reference project, from network to report.

These are captures from the live interface, not mock-ups. The set follows the same 11 kV case from topology and harmonic baseline through branch design, simulation, impedance scan and limit check to the issued report.

System modeling screen with project and supply data, PCC limits, load list and live calculation results
Network topology screen with GRID, 11 kV bus, four load groups and FC1 to FC4 filter branches
Harmonic data screen with THDi, THDu, current and voltage pass counts and order-by-order table
Filter design screen with branch configuration table and design results table
Simulation screen with current and voltage harmonic spectra, filter rate and limit result
Impedance scan screen with topology, scan settings, curve and top-ten resonance peaks
Limit check table from the 2nd to the 50th harmonic with current and voltage limits and pass results
Deliverables screen with report export buttons and calculation summary

Input once, calculate immediately

Project and supply, PCC and limits, the load list and the live calculation results sit on one screen. Short-circuit current, system impedance and the compensation requirement update as the inputs change, so the model never lives in two places.

11 kV · 481.6 MVA · 25.28 kA · 3,388 kvar · THDu 2.97%

The drawing is the calculation model

GRID, the 11 kV bus, four load groups and FC1 to FC4 are placed on one canvas. Power flow, branch current and harmonic data are written back onto every element, so the topology, the calculation and the exported DXF stay on the same data path.

BUS-1 10.911 kV · Δ -0.81% · 4 loads · FC1–FC4 · 3,282.2 kvar

Establish the baseline before sizing anything

The unfiltered case is measured against the selected framework: current THD, voltage THD, Isc/IL and every order from 2 to 50. Orders outside the limit are flagged individually, so the design starts from the real weak points rather than a single total.

THDi 12.18% · THDu 2.97% · current 43/49 · voltage 49/49

Branch data and the resulting duty in one table

Tuned order, filter type, series sections, parallel units, wiring, capacitor voltage rating and per-phase output are calculated for each branch. The reference case uses four branches and reaches 3,282.84 kvar at the fundamental.

4 branches · 5th / 7th / 11th / 13th · 3,282.84 kvar

Prove the result against the limit, order by order

After filtering, the current spectrum and the voltage spectrum are checked against the same limit set. The summary and the per-order table come from one run: 12.18% to 4.48% current THD, 2.97% to 1.17% voltage THD, 63.2% harmonic current removed, 49/49 checks passed.

THDi 4.48% · THDu 1.17% · filter rate 63.2% · 49/49 passed

See the resonance points before the site does

The impedance scan runs from the first to the 100th order with the filter branches in service. The curve, the scanned points and the top-ten peaks share the same model; the result can be exported to XLSX for the study file.

1–100 orders · peaks 6.60th / 8.84th · XLSX export

One table for every order and every limit

The limit check lists the 2nd to the 50th order with current distortion, voltage content, the IEEE 519-2014 limits and the IEC planning-level columns. Each row ends in a pass or fail conclusion, so a reviewer can see exactly which order was assessed and against what.

2–50 orders · all 49 checks pass · IEEE 519-2014 + IEC

Issue the package from the checked project

Report Center exports the Excel calculation book, CSV summary, Word proposal and legacy report from the same data set. The issued summary carries the same 2.97% to 1.17% result and the same 49/49 pass count, so the document cannot drift from the model.

DOCX · XLSX · CSV · DXF · ETAP exchange

Some field labels in these captures still show Chinese; a later iteration will complete a full localization pass across all six interface languages.

Simulation

Simulation is not an appendix. It is the main capability.

Power flow, harmonic spectra, impedance scans and limit checks share one engine. A passing total THDu does not hide a failing individual order — both views are on the same result set.

Current and voltage spectrum, before and after filtering

Same run
Harmonic current spectrum before and after filtering with the IEEE limit line
Reference project: 11 kV PCC, 481.9 A load current, four branches at the 5th, 7th, 11th and 13th. Current THD falls from 12.18% to 4.48%; voltage THD from 2.97% to 1.17%.
What the engine reports
63.2%harmonic current removed

The current filter removes 63.2% of the harmonic current in the reference case, while the voltage THD moves comfortably below the 5.0% planning limit.

  • 01PCC power flow, voltage deviation and branch flows
  • 02Harmonic current and voltage, 2–50 orders
  • 03Impedance scan, 1–100 orders, with resonance peaks
  • 04Limit check per order, with exceedance highlighted
  • 05Branch overload and capacitor duty check
Standards

One assessment engine, three recognised frameworks.

International projects usually start from IEEE 519-2014 or an IEC planning level. The platform keeps the framework visible, so the report states which limit was applied and where.

Framework
Typical use
What HY-PQD Studio evaluates
IEEE 519-2014
Primary
Industrial and utility interconnection studies, especially where the purchaser specifies IEEE.
Current distortion limits from Isc/IL, TDD, individual harmonic current limits, voltage distortion and per-order pass/fail. The reference project uses this framework at the 11 kV PCC.
IEC 61000-3-6 / 3-12
International
Planning levels for MV and LV networks, and equipment connection assessment in IEC markets.
Voltage planning levels, harmonic current allocation and stage-based assessment for networks specified to IEC 61000.
GB/T 14549
Optional
China-based projects where the local authority or utility requires the national standard.
Available as an additional check for domestic Chinese projects. It is not the default framework for export or international work.

Standards are assessment frameworks, not certifications. The responsible engineer confirms the applicable limit, the point of assessment and the utility’s interpretation before issuing the design.

Deliverables

The package a reviewer can actually check.

Every export is generated from the same project. Inputs, branch design, simulation results and conclusions remain consistent across the Word proposal, the Excel workbook and the drawing.

DOCX
Technical proposalSystem description, filter configuration, simulation summary and compliance statement.
XLSX
Calculation bookParameters, load list, branch design, power flow, harmonics and limit checks on separate sheets.
CSV
Result summaryCompact data set for review, archiving or import into another study.
DXF
Single-line diagramDrawing exported from the same topology used for the calculation.
ETAP
Topology exchangeImport and export of network topology data for ETAP-based workflows.

One platform, six working languages

Engineering teams and reviewers can work in the interface they already use. The project data and calculation results stay the same when the language changes.

EnglishChineseJapaneseFrenchRussianSpanish
Reference case · Australia

11 kV PCC · 481.6 MVA short-circuit · 25.28 kA · 7,418.8 kW load · 3,388 kvar configured · THDu 2.97% → 1.17% · 49/49 checks passed.

Bring us a network and a harmonic limit.

Send the PCC data, the load list, the governing standard and the target power factor. We will show the model, the filter selection and the limit result on your own case.